9:AM – 5:PM

Monday to Friday

Dallas, Texas 75001

Houston, Texas 77001

(833) 4MY-RATE

December 21, 2024

9:AM – 5:PM

Monday to Friday

Dallas, Texas 75001

Houston, Texas 77001

(833) 4MY-RATE

GEP Calculations

“CALCULATIONS”

Single phase circuit calculation

Power factor calculation:

PF = |cos φ| = 1000 × P(kW) / (V(V) × I(A))

Apparent power calculation:

|S(kVA)| = V(V) × I(A) / 1000

Reactive power calculation:

Q(kVAR) = √(|S(kVA)|2P(kW)2)

Power factor correction capacitor’s capacitance calculation:

C(F) = 1000 × Q(kVAR) / (2πf(Hz)×V(V)2)

Three phase circuit calculation

For three phase with balanced loads:

Calculation with line to line voltage

Power factor calculation:

PF = |cos φ| = 1000 × P(kW) / (3 × VL-L(V) × I(A))

Apparent power calculation:

|S(kVA)| = 3 × VL-L(V) × I(A) / 1000

Reactive power calculation:

Q(kVAR) = √(|S(kVA)|2P(kW)2)

Power factor correction capacitor’s capacitance calculation:

C(F) = 1000 × Q(kVAR) / (2πf(Hz)×VL-L(V)2)

Calculation with line to neutral voltage

Power factor calculation:

PF = |cos φ| = 1000 × P(kW) / (3 × VL-N(V) × I(A))

Apparent power calculation:

|S(kVA)| = 3 × VL-N(V) × I(A) / 1000

Reactive power calculation:

Q(kVAR) = √(|S(kVA)|2P(kW)2)

Power factor correction capacitor’s capacitance calculation:

C(F) = 1000 × Q(kVAR) / (3×2πf(Hz)×VL-N(V)2)

Top